Description
Key Specifications:
- Set Point Range C: −6C to 26.6C
- Temperature Stability: /−0.6C
- Power Requirements: 230V, 3 phase, 60Hz, 35.2 A
- Reservoir Capacity (gallons): 11 gallons
- Reservoir Capacity (liters): 42 Liters
- Low Liquid Level Alarm: Yes
- Pump Type: 1.5HP stainless steel Displacement pump
- Maximum Pump Pressure: 35 psi
- Maximum Flow Rate: 12 gpm
- Refrigerant Type: R410A
- processonnections: 1.5
- Cooling Capacity @ 35C: 17935 W / 61,200 BTU/hr
- Cooling Capacity @ 10C: 5500 W
- Cooling Capacity @ 5C: 4600 W
- Cooling Capacity @ 2C: 4200 W
- Cooling Capacity @ 1C: 3800 W
- Cooling Capacity @ −4C: 400 W
- Cooling Capacity @ −6C: 3100 W
Key Features:
- Compact micro−channel all aluminum air−cooled condensers for increased durability
- High efficieny, low nosie fans (air−cooled units only) with integral conensers for reduced operating noise and increased efficiency
- Stainless steel brazed plate evaporators with flow and temperature safeties to gaurd against freezing
- Low voltage 24 VDC control keeps the control circuit signals free from AC interference
- C−UL 508A industial control panel with single point electrical connection
- Removable inlet air filter is easily cleaned and protects condenser coils to assume maxium efficieny
- High capacity cooling for plasma torch cutting, machine tool hydraulics, high powered lasers, and other high heat generating processes and equipment
- Displays temperature and pressure or flow rate simultaneously
- User−adjustable temperature, pressure, and flow rate alarms
- Simple operation and maintenance
Controller Features:
- Password protected operational parameters
- Start−tostart anti−cycle timer prevents short−cycling of compressor while minimizing unnecessary off periods
- Display of compressor and pump running hours helps with scheduling routine maintenance
- Loss of phase/phase reversal/phase imbalance alarm
- Pump test button allows for quick and easy pump rotation check from the main control panel
- Temperature deviation warning provide an adjustable deviation set point to indicate abnormal operation of chiller or processquipment without shutting down